Materials:
Where cz 01 series differs is in the way it ensures goodgrounding of thetanker to the gantry and ensuresdissipation of static electricityandso eliminatessparks.Hence the name "Ground Boss".lthas long been a recommendedpractice to break thenumber 10 common earth return and""force" it through thetanker frame by terminating and bolting the wire through thetank at a distance apart to ensure grounding of the tank.However the difficulty in doing this cheaply and neatly hasmeant that only a few tankers use the technique."Ground Boss" achieves this at essentially no cost by usingthe mountingbolts inside the plug. internalinsulatingbushes ensure the only electrical path is via the externalfastener,i.e. those bolted to the tanker: and the number 10common earth wire is run from pin 10 to one bolt head andfrom under the other bolt head via conduit to the probes.9and 10 are simply looped together if required.Therefore theonly way the tanker can load is by having its tank in goodcontact with the rack monitor earth.
Features &Benefits:
3 and 4 bayonet fixing to industry standard
10 pin as standard
Conduit ports 1/2"NPT(straight) thread,two options
Mounting by 2 stainless steel bolts 8mm dia.via Delrin insulating bushes
cZ01103- 3 pin bayonet fastening
Weight-1.3kg.
Aluminium nose-cone,hard anodised
Stainless steel pins and terminator